U-Value Calculator
Calculate the thermal transmittance (U-value) of composite multi-layer walls, roofs, and floors. Build custom assemblies with real thermal conductivity values (λ), compute total thermal resistance (Rtot), and visualize temperature gradients.
🧱 Multi-Layer Construction Stack (From Inside to Outside)
| Material Layer | Thickness (mm) | Conductivity λ (W/mK) | Resistance R |
|---|
🌡️ Cross-Sectional Thermal Drop Profile
Thermal Resistance (BS EN ISO 6946)
Material Thermal Conductivity (λ) & Thickness Matcher
Compare how much physical thickness is required across different materials to hit a target thermal resistance of R-5.0 m²K/W (U = 0.20 W/m²K).
Insulation Thickness vs. U-Value Diminishing Returns Simulator
Slide insulation thickness to observe how the first 50mm delivers the overwhelming majority of energy savings.
UK Building Regulations Part L (2021) Limiting U-Values
Statutory maximum U-values for new residential dwellings and major thermal renovations in England & Wales.
| Building Element | Target U-Value (W/m²K) | Limiting Maximum (W/m²K) | Passivhaus Benchmark |
|---|---|---|---|
| External Walls | 0.18 W/m²K | 0.26 W/m²K | ≤ 0.15 W/m²K |
| Pitched Roof (Insulated at Ceiling) | 0.11 W/m²K | 0.16 W/m²K | ≤ 0.12 W/m²K |
| Flat Roof / Rafter Slope | 0.11 W/m²K | 0.16 W/m²K | ≤ 0.12 W/m²K |
| Ground Floor | 0.13 W/m²K | 0.18 W/m²K | ≤ 0.15 W/m²K |
| Windows & Glazed Doors | 1.20 W/m²K | 1.60 W/m²K | ≤ 0.80 W/m²K |
5 Common U-Value Calculation Mistakes
Avoid these frequent errors when modeling multi-layer composite structures.
1. Forgetting Surface Air Films (R_si & R_se)
Omitting the internal (0.13 m²K/W) and external (0.04 m²K/W) boundary air films causes a 5%–15% error in uninsulated and thin assembly calculations.
2. Ignoring Timber Stud Repeating Thermal Bridges
In timber stud walls, softwood studs represent 15% of the wall area. Because timber has a higher thermal conductivity (λ=0.13) than mineral wool (λ=0.038), it creates a bridging penalty.
3. Adding U-Values Directly
You cannot add U-values together (1/U_total ≠ U1 + U2). You must sum thermal resistances (R_total = R1 + R2 + ...), and then invert the total: U = 1 / R_total.
4. Using Nominal Instead of Declared Lambda
Always use aged declared thermal conductivity values (λ_90/90) that account for long-term gas diffusion in foam insulations.
Related Building Physics Tools
Explore imperial R-value conversions, single-room conduction calculations, and convective air permeability modeling.
Room Heat Loss Calculator
Calculate precise heat loss for individual rooms to size replacement radiators.
R-Value to U-Value Converter
Instantly convert between imperial R-values (hr·ft²·°F/BTU) and metric U-values.
Air Infiltration / ACH Calculator
Estimate ventilation and air leakage heat loss based on air changes per hour.
U-Value & Thermal Assembly FAQs
Expert answers on multi-layer thermal resistance, surface air film coefficients, and Part L building regulation compliance.